| Plan Review Notes For Permit 00081726 |
| Permit Number |
00081726 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. THE USE OF CO2 SENSORS TO REDUCE THE | | | AMOUNT OF OUTSIDE AIR REQUIRED BY ASHRAE | | | 62-89 IS NOT SPECIFIED AS AN ALTERNATIVE | | | METHOD. ACCEPTABLE REDUCTION METHODS ARE | | | GIVEN IN 6.1.3.4 INTERMITTENT OR | | | VARIABLE OCCUPANCY. "PEAK OCCUPANCIES OF | | | LESS THAN THREE HOURS DURATION" AND WHEN | | | "PROVIDED THE AVERAGE OCCUPANCY USED IS | | | NOT LESS THAN ONE-HALF THE MAXIMUM. | | | THE USE OF CO2 SENSORS TO REDUCE REQUIRE | | | AMOUNTS OF OUTSIDE AIR DOES NOT TAKE INT | | | CONSIDERATION THE EFFECTS OF POSSIBLE | | | ELEVATION OF OTHER CONTAMINANTS. | | | 2. DRAWING M 2.1 SHOWS AUX. PAN DRAIN | | | CONNECTED TO PRIMARY CONDENSATE DRAIN | | | LINE. DETAIL IN CIRCLE DOES NOT SHOW | | | THIS. NOTE THAT AUX DRAIN LINE SHALL NOT | | | BE CONNECTED TO PRIMARY DRAIN LINE. |
|