Plan Review Notes
Plan Review Notes For Permit 00081726
Permit Number 00081726
Review Stop M
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************DENIED********************
 1. THE USE OF CO2 SENSORS TO REDUCE THE
 AMOUNT OF OUTSIDE AIR REQUIRED BY ASHRAE
 62-89 IS NOT SPECIFIED AS AN ALTERNATIVE
 METHOD. ACCEPTABLE REDUCTION METHODS ARE
 GIVEN IN 6.1.3.4 INTERMITTENT OR
 VARIABLE OCCUPANCY. "PEAK OCCUPANCIES OF
 LESS THAN THREE HOURS DURATION" AND WHEN
 "PROVIDED THE AVERAGE OCCUPANCY USED IS
 NOT LESS THAN ONE-HALF THE MAXIMUM.
 THE USE OF CO2 SENSORS TO REDUCE REQUIRE
 AMOUNTS OF OUTSIDE AIR DOES NOT TAKE INT
 CONSIDERATION THE EFFECTS OF POSSIBLE
 ELEVATION OF OTHER CONTAMINANTS.
 2. DRAWING M 2.1 SHOWS AUX. PAN DRAIN
 CONNECTED TO PRIMARY CONDENSATE DRAIN
 LINE. DETAIL IN CIRCLE DOES NOT SHOW
 THIS. NOTE THAT AUX DRAIN LINE SHALL NOT
 BE CONNECTED TO PRIMARY DRAIN LINE.