| 2001-01-08 00:00:00 | 1)TITLE SHEET-CODE INFORMATION-NOTE |
| | STANDARD PLUMBING CODE W/1999 COUNTYWIDE |
| | AMENDMENTS. |
| | |
| | 2)SUBMIT SQUARE FOOTAGE OF HABITABLE |
| | FLOOR SPACE TO SHOW COMPLIANCE W/SPC |
| | TABLE 407.SEE SPC SEC.407.1.3. FOR |
| | ALLOWED DEUCTIBLE AREAS.ADDITIONAL |
| | PLUMBING FIXTURES MAY BE REQD. |
| | |
| | 3)DOOR CANNOT SWING INTO CLEAR FLOOR |
| | SPACE FOR LAV.IN MEN'S TOILET ROOM PER |
| | FACBC SEC.4.22.2. |
| | |
| | 4)MAX.HT.OF LAVATORY TO RIM SHALL BE 34" |
| | PER FACBC SEC.4.19.2. |
| | |
| | 5)FLOOR DRAINS IN TOILET ROOM SHALL BE A |
| | MIN.OF 3" PER SPC SEC.409.4.1.1. |
| | |
| | 6)TERMINATION PT.OF T & P LINE SHALL |
| | COMPLY W/COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.507.8.4.THE LINE SHALL NOT DISCHARGE |
| | TO CD. |
| | |
| | 7)WATER CLOSETS AND FLOOR DRAINS ARE NOT |
| | PROPERLY VENTED.COMPLY W/SPC SEC. |
| | 906.2.1. |
| | |
| | 8)CLEANOUTS SHALL BE INSTALLED PER SPC |
| | SEC.710.2.1. |
| | |
| | 9)SHT.M3.0 REFERS TO GAS SYSTEM.IF NOT |
| | APPLICABLE REMOVE FROM PLANS. |
| | |
| | 10)EACH SHEET WHICH MUST BE SEALED BY |
| | THE PROFESSIONAL ENGINEER SHALL LEGIBLY |
| | INDICATE THEIR NAME,ADDRESS AND NUMBER |
| | ON EACH SHEET PER FLA.ADMIN.CODE |
| | 61G15-23.002. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |