Plan Review Notes
Plan Review Notes For Permit 00081726
Permit Number 00081726
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:
 1.PROVIDE INFORMATION ON O/A DAMPER
 CAPACITIES (MAX AND MIN)
 DO NOT REDUCE OUTSIDE AIR BELOW
 VALUES SHOWN ON M2.0 ( 1940 CFM) BY CO2
 SENSOR. 1940 CFM IS MINIMUM REQUIRED
 VOLUME PER ASHRAE 62-89 TABLE 2.
 2 PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3.CONDENSATE DRAIN LINE AND EMERGENCY
 OVERFLOW DRAIN LINE SHALL NOT CONNECT
 TOGETHER. OVERFLOW DRAIN LINE SHALL
 TERMINATE IN A CONSPICOUS LOCATION. 1997
 SMC 304.8.6.1
 4. NOTE: RETURN AIR PLENUM AREA ABOVE
 CEILING TO BE CONSTRUCTED ENTIRELY OF
 NONCOMBUSTIBLE MATERIALS. PER 1997 SMC
 609.1.1