| Plan Review Notes For Permit 00081726 |
| Permit Number |
00081726 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED: | | | 1.PROVIDE INFORMATION ON O/A DAMPER | | | CAPACITIES (MAX AND MIN) | | | DO NOT REDUCE OUTSIDE AIR BELOW | | | VALUES SHOWN ON M2.0 ( 1940 CFM) BY CO2 | | | SENSOR. 1940 CFM IS MINIMUM REQUIRED | | | VOLUME PER ASHRAE 62-89 TABLE 2. | | | 2 PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3.CONDENSATE DRAIN LINE AND EMERGENCY | | | OVERFLOW DRAIN LINE SHALL NOT CONNECT | | | TOGETHER. OVERFLOW DRAIN LINE SHALL | | | TERMINATE IN A CONSPICOUS LOCATION. 1997 | | | SMC 304.8.6.1 | | | 4. NOTE: RETURN AIR PLENUM AREA ABOVE | | | CEILING TO BE CONSTRUCTED ENTIRELY OF | | | NONCOMBUSTIBLE MATERIALS. PER 1997 SMC | | | 609.1.1 |
|