| Plan Review Notes For Permit 00081726 |
| Permit Number |
00081726 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | | FOR FIRE SPRINKLER PLAN. | | | 2) NO FIRE ALARM EQUIPMENT SHOWN ON | | | PLANS. HOW IS BASE BUILDING FIRE ALARM | | | SYSTEM HEARD WITHIN TENANT SPACE. | | | 3) PROVIDE EMERGENCY LIGHTING IN | | | STOCKROOM. | | | 4) EXITING PERMITTED IN STOCKROOM IF THE | | | FOLLOWING CONDITIONS EXIT, DOOR LEADING | | | TO STOCKROOM CANNOT BE LOCKED, AN AISLE | | | OF AT LEAST 44" WIDE IS TO BE PROVIDED | | | AND MAINTAINED, AND NOT MORE THAN 50 | | | PERCENT OF THE EXIT ACCESS IS TO BE | | | PROVIDED THROUGH STOCKROOM. | | | 5) FIRE EXTINGUISHERS ARE TO BE PROVIDED |
|