Plan Review Notes
Plan Review Notes For Permit 00081726
Permit Number 00081726
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO HYDRAULIC CALCULATIONS PROVIDED
 FOR FIRE SPRINKLER PLAN.
 2) NO FIRE ALARM EQUIPMENT SHOWN ON
 PLANS. HOW IS BASE BUILDING FIRE ALARM
 SYSTEM HEARD WITHIN TENANT SPACE.
 3) PROVIDE EMERGENCY LIGHTING IN
 STOCKROOM.
 4) EXITING PERMITTED IN STOCKROOM IF THE
 FOLLOWING CONDITIONS EXIT, DOOR LEADING
 TO STOCKROOM CANNOT BE LOCKED, AN AISLE
 OF AT LEAST 44" WIDE IS TO BE PROVIDED
 AND MAINTAINED, AND NOT MORE THAN 50
 PERCENT OF THE EXIT ACCESS IS TO BE
 PROVIDED THROUGH STOCKROOM.
 5) FIRE EXTINGUISHERS ARE TO BE PROVIDED