| Plan Review Notes For Permit 00081726 |
| Permit Number |
00081726 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1.SHEET A0.1 | | | CHANGE CODE REFRENCE TO SBC 1997 | | | EDITION. | | | BUILDING CONST.IS TYPE 2 NOT TYPE 4 | | | 2.SHEET A5.2 SECTION 13 NOTE AT TOP | | | SHOWS 5/8 INCH PLYWOOD & NOTE AT | | | BOTTOM SHOWS 1/2 PLYWOOD PLEASE | | | CLARIFY? | | | 3.SUBMIT WALL SECTION SHOWING TENANT | | | DENIZING WALLS FIRE RATING AND UL # | | | | | | 4.SUBMIT FIRE SPRINKLER PLANS AND | | | APPLICATION FROM SPRINKLER CONTRACTOR. | | | 5.SUBMIT PRODUCT APPROVAL FOR WINDOW & | | | DOOR GLAZING FOR STOREFRONT/ MTERO | | | DADE COUNTY OR SBCCI SSTD12-97. | | | | | | PROVISO | | | 1) ALL WOOD TO BE FRT PER SP.3 SECTION | | | 06100. | | | 2) SIGNS TO BE UNDER SEPERATE PERMIT |
|