| 2001-01-08 00:00:00 | ************* REVISION REQ'STED ******** | | | | | | 1)NOTE: PLEASE SHOW BLDG. STEEL AS PART | | | OF THE GROUNDING ELECTRODE SYSTEM PER | | | 250-50 ON RISER DIAGRAM. | | | | | | 2)NOTE: PLEASE SHOW AIC RATINGS OF MAINS | | | AND PANEL. PER 110-9 AND 215-5 | | | | | | PLEASE SUBMIT AND SHOW ALL THE ABOVE | | | INFORMATION ON PLAN BEFORE ROUGH ELECTR- | | | -ICAL INSPECTION IS CALLED IN. IF THERE | | | ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|