| 2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM PRIOR | | | REVIEWS. NOT ALL NOTES WERE ADDRESSED??? | | | | | | 2)NOTE: PLEASE SEE RISER, PANEL SHOWS | | | IT AS MCB? AND PANEL SCHEDULE SHOWS MLO? | | | PLEASE CORRELATE. | | | | | | 3)NOTE: PLEASE SEE THAT NO AIC RATINGS | | | FOR MAIN DISCONNECT OR PANEL WERE SHOWN? | | | MAINS AND PANELS MUST BE RATED FOR THE | | | AVAILABLE FAULT CURRENT. PER 110-9. | | | | | | 4)NOTE: AS ON PRIOR REVIEW PLEASE SHOW | | | NEW BLDG STEEL AS PART OF THE GROUNDING | | | ELECTRODE SYSTEM. PER 250-50 FOR | | | NEW BLDG FOOTERS.!! | | | | | | 5)NOTE: PLEASE SEE NOTES FROM BLDG AND | | | MY REVIEW. SEE F.A.C 61G16 AND 481.221 | | | PLANS ARE SIGNED,SEALED AND DATED. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 659-8096 EXT 8372 |
|