2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE NOTES FROM PRIOR
 REVIEWS. NOT ALL NOTES WERE ADDRESSED???
  
 2)NOTE: PLEASE SEE RISER, PANEL SHOWS
 IT AS MCB? AND PANEL SCHEDULE SHOWS MLO?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE THAT NO AIC RATINGS
 FOR MAIN DISCONNECT OR PANEL WERE SHOWN?
 MAINS AND PANELS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT. PER 110-9.
  
 4)NOTE: AS ON PRIOR REVIEW PLEASE SHOW
 NEW BLDG STEEL AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. PER 250-50 FOR
 NEW BLDG FOOTERS.!!
  
 5)NOTE: PLEASE SEE NOTES FROM BLDG AND
 MY REVIEW. SEE F.A.C 61G16 AND 481.221
 PLANS ARE SIGNED,SEALED AND DATED.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372