Plan Review Notes
Plan Review Notes For Permit 00081675
Permit Number 00081675
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SEE 680-6-A-2 FOR NOTE
 SHOWN FOR POOL AREA. PLEASE ADJUST PLAN
 NOTE.
  
 2)NOTE: NOW THAT YOU HAVE SUBMITTED A
 RISER DIAGRAM SHOWING ALL NEW SERVICE
 BEING INSTALLED, PLEASE SUBMIT AIC
 RATINGS FOR ALL EQUIPMENT BEING INSTALL-
 -ED. MIAN DISC/ AND PANEL MUST BE RATED
 FOR THE AVAIABLE FAULT CURRENT PER 110-9
 AND 215-5.
  
 3)NOTE: PLEASE SEE ART 384-7 AND 110-26
 OF THE NEC. NEW PANEL SHOWN IN BATHROOM
 CLOSET MAY NOT BE INSTALLED IN THAT
 LOCATION. PLEASE ADJUST LOCATION AND
 MAKE CHANGES TO PLAN.
  
 4)NOTE: PER 250-50 NEW BLDG STEEL MUST
 BE BONDED TO GROUNDING ELECTRODE CONDUC-
 -TOR.PLEASE SHOW ON RISER DIAGRAM 215-5
  
  
 5)NOTE: PLEASE SEE THE REQ`MENTS PER FL
 ADMINISTATIVE CODE FOR PLANS TO CONTAIN
 INFORMATION ON ARCH OF RECORD. PLEASE
 CLARIFY FRANCIS DIGIOVANI? IS THIS THE
 FIRM UNDER WHICH PATRICK SEAGRAVES WORKS
 ?? PLEASEDATE THE SIGNED AND SEALED
 PLAN. ALL PER 61G16 AND 471.221.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372