Plan Review Notes For Permit 00081675
Permit Number 00081675
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY,PLANS STAMPED BY THEM AND RECEIPT
 SUBMITTED TO CITY OF WPB BLDG. DEPT.
  
 2)PROVIDE ATTIC ACCESS PER 97 SBC 2309.6
  
 3)BATHROOM WINDOWS MUST COMPLY WITH
 SAFETY GLAZING REQUIREMENTS PER 97 SBC
 2405.2.
  
 4)PLEASE SPECIFY TRUSS ANCHORS FOR TRUSS
 -ES AT REAR WITH 705# UPLIFT.
  
 5)NOTE 5 ON SHEET S-1 IS INCORRECT. THE
 WINDLOAD FOR PALM BEACH CO. IN ASCE7-95
 IS 140 MPH,NOT 110 MPH. PLEASE RECHECK
 YOUR CALCULATIONS.
  
 6)IF STRUCTURE IS NOT DESIGNED BY AN
 ARCHITECT OR ENGINEER,THE DESIGN MUST
 CONFORM TO SSTD 10-97,WHICH IS THE
 PRESCRIPTIVE STANDARD ADOPTED BY THE
 CITY OF WPB. CITY AMENDMENTS TO 97 SBC.
 SEC.104.2.3. PLEASE REVIEW PLANS FOR
 COMPLIANCE WITH SSTD 10-97 AND DO NOT
 SITE OTHER DESIGN CRITERIA ON PLANS.
 IF DESIGNED BY ARCHITECT OR ENGINEER
 PLANS MUST BE SIGNED,SEALED AND DATED.
  
 7)PROVIDE EAST AND WEST ELEVATIONS
 SHOWING ALL OPENINGS IN NEW AND EXISTING
 STRUCTURE,SO THAT THE PERCENTAGE OF
 ALLOWABLE OPENINGS CAN BE DETERMINED PER
 97 SBC TABLE 600.
  
 8)PROVIDE 2 CURRENT COPIES OF METRO-DADE
 OR SBCCI PRODUCT APPROVALS FOR FRENCH
 DOORS WITH SIDELITES AS SHOWN ON REAR
 ELEVATION ON PLANS. IMPACT GLASS OR
 OTHER IMPACT PROTECTION WILL BE REQUIRED
  
 9)PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE,WITH SPECIFIC ANCHORS TO BE
 USED,FOR STORM PANELS.