2001-01-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT CLARIFICATION ON
 SERVICE CONDUCTOR SIZE. YOU SHOW #1.
 PLEASE SEE 310-15 AND 310-16
  
 2)NOTE: MISSING A/C DISC`S PER 440-11
  
 3)NOTE:PLEASE LIST REQ`D BATH(S) CIRCUIT
 (S) PER 210-11-C-3 ON PANEL SCHEDULE..
  
 4)NOTE: PLEASE SEE LOAD CALCUALTIONS.
 CALCS DO NOT CORRELATE WITH MECHANICAL
 PLANS OR ELECTRICAL A/C PLAN LAYOUT.
 215-5.
  
 5)NOTE: PLEASE SEE SQ FT BEING ADDED ON
 BLDG PLANS. THIS ALSO DOES NOT CORRELATE
 WITH LOAD CALCULATIONS FOR SQ FT/GEN LT.
 PER 220
  
 6)NOTE: PLEASE SEE SMALL APPLIANCE
 CALCSSHOWN. YOU SHOW 4.5 KW AND ONLY
 TWO CIRCUITS. PLEASE CLARIFY.
  
 7)NOTE: PLEASE SEE RISER DIAGRAM AND
 CORRELATE WITH ELECTRICAL PLAN. WHERE
 IS THE SECOND PANEL GOING? PLEASE
 SUBMIT CLARIFICATION ON SERVICE.
 NOTE ON ELECTRICAL PLAN SAYS CIRCUITS
 ARE BEING FED TO EXISTING 200 AMP
 FUSE PANEL.? RISER DIAGRAM DOES NOT
 SHOW THIS.
  
 8)NOTE: MISSING WP GFI REC FOR A/C CU`S.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 659-8096 EXT 8372