| 2001-01-08 00:00:00 | **************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SUBMIT CLARIFICATION ON |
| | SERVICE CONDUCTOR SIZE. YOU SHOW #1. |
| | PLEASE SEE 310-15 AND 310-16 |
| | |
| | 2)NOTE: MISSING A/C DISC`S PER 440-11 |
| | |
| | 3)NOTE:PLEASE LIST REQ`D BATH(S) CIRCUIT |
| | (S) PER 210-11-C-3 ON PANEL SCHEDULE.. |
| | |
| | 4)NOTE: PLEASE SEE LOAD CALCUALTIONS. |
| | CALCS DO NOT CORRELATE WITH MECHANICAL |
| | PLANS OR ELECTRICAL A/C PLAN LAYOUT. |
| | 215-5. |
| | |
| | 5)NOTE: PLEASE SEE SQ FT BEING ADDED ON |
| | BLDG PLANS. THIS ALSO DOES NOT CORRELATE |
| | WITH LOAD CALCULATIONS FOR SQ FT/GEN LT. |
| | PER 220 |
| | |
| | 6)NOTE: PLEASE SEE SMALL APPLIANCE |
| | CALCSSHOWN. YOU SHOW 4.5 KW AND ONLY |
| | TWO CIRCUITS. PLEASE CLARIFY. |
| | |
| | 7)NOTE: PLEASE SEE RISER DIAGRAM AND |
| | CORRELATE WITH ELECTRICAL PLAN. WHERE |
| | IS THE SECOND PANEL GOING? PLEASE |
| | SUBMIT CLARIFICATION ON SERVICE. |
| | NOTE ON ELECTRICAL PLAN SAYS CIRCUITS |
| | ARE BEING FED TO EXISTING 200 AMP |
| | FUSE PANEL.? RISER DIAGRAM DOES NOT |
| | SHOW THIS. |
| | |
| | 8)NOTE: MISSING WP GFI REC FOR A/C CU`S. |
| | |
| | PLEASE SUBMIT ALL THE ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | 659-8096 EXT 8372 |