| 2001-01-08 00:00:00 | SECOND CHECKLIST: |
| | 1-IMPACT FEES STILL NOT PAID. |
| | 2-SECOND FLOOR WINDOWS IN BEDROOM #2 |
| | DON'T COMPLY WITH SECTION 1005.4.4 OF |
| | SBC 1997. MINIMUM CLEAR OPENING TO BE |
| | 5.7 SQ. FT.(26 1/2"BY 31 1/2" WINDOW |
| | DON'T PROVIDE THE MINIMUM CLEAR |
| | OPENING) |
| | -SIZE OF WINDOW SPECIFIED ON DWG A-1.0 |
| | IS NOT CLEAR? WHAT IS (3)1H5 SH.? SEE |
| | PLANS. |
| | 3-PROVIDE SIGNED AND SEALED SOIL TEST |
| | REPORT FOR THIS LOT. SEE ORIGINAL SOIL |
| | TEST REPORT FOR RECOMMENDATIONS. |
| | -IF ORGANIC MATERIALS ARE PRESENT, THEN |
| | THEY NEED TO BE REMOVED.SEC 1804.1.8 |
| | OF SBC 1997. |
| | 4-PROVIDE PRODUCT APPROVALS FOR: |
| | -SKYLIGHT (EXPIRED). |
| | -FLAT ROOF SYSTEM. |
| | -ENTRY DOOR WITH SIDELITE ASSEMBLY WITH |
| | COMPLETE AND LEGIBLE DRAWINGS. |
| | -WINDOW MULLIONS. |
| | -ONE HOUR GLASS BLOCK. |
| | -SLIDING GLASS DOOR WITH TRANSOM ABOVE |
| | ASSEMBLY. |
| | 5-TRUSS DRAWINGS: |
| | -TRUSS ENGINEER TO PROVIDE ORIGINAL |
| | SIGNATURE WHEN SUBMITTING DOCUMENTS |
| | FOR PUBLIC RECORDS AS PER CHAPTER 471 |
| | OF FLORIDA STATUTES. |
| | -TRUSS ENGINEER TO UPDATE ALL GENERAL |
| | DETAILS AND SIGN, SEAL AND DATE THEM. |
| | DON'T PROVIDE COPIES SIGNED BY ANOTHER |
| | ENGINEER. DRAWINGS TO BE LEGIBLE ALSO. |
| | -TRUSS ENGINEER TO REVISE FLOOR TRUSSES |
| | BY THE FOYER AREA AS PER INSTRUCTIONS |
| | OF ENGINEER OF RECORD. SEE SHEET S-1. |
| | -ENGINEER OF RECORD TO REVIEW ALL TRUSS |
| | DRAWINGS PRIOR TO SUBMITTAL TO THIS |
| | OFFICE. |
| | *NOTE: SHOP DRAWINGS REVIEW STAMP |
| | BY ENGINEER OF RECORD DOESN'T SHOW THE |
| | NAME OF THE COMPANY REVIEWING THE |
| | SHOP DRAWINGS. |
| | 6-ENGINEER OF RECORD TO SPECIFY ALL |
| | CONNECTORS. SEE ROOF FRAMING PLAN FOR |
| | COMMENTS. |
| | 7-PROVIDE BUCK DETAIL FASTENING FOR A |
| | 2X BUCK. PRODUCTAPPROVAL FOR DOORS |
| | AND WINDOWS REQUIRE A 2X BUCK. SEE |
| | PRODUCT APPROVALS. |
| | 8-STORM PANELS: |
| | -PROVIDE COMPLETE INFORMATION FOR STORM |
| | PANELS. |
| | -THIS MAY BE SUBMITTED LATER UNDER A |
| | SEPARATE PERMIT. |
| | 9-REVISE SIZE OF CEILING FANS. SEE TABLE |
| | 6-6 OF FLORIDA ENERGY EFFICIENCY CODE |
| | FOR BUILDING CONSTRUCTION. 1997 ED. |
| | 10-SEE COMMENTS ON PLANS, INCLUDING |
| | COMMENTS BY THE OTHER TRADES AND |
| | REVISE ORIGINALS AS REQUIRED. |
| | |
| | |
| | |
| | |
| | NOTES: |
| | -PLEASE RETURN REVIEWED SET AFTER |
| | CORRECTIONS ARE DONE TO ORIGINALS IN |
| | ORDER TO EXPEDITE THE REVIEW PROCESS. |
| | -IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT 659-8096 EXT. 8232. |
| | |
| | |
| | ****CONTRACTOR TO RENEW LICENSE. |