| Plan Review Notes For Permit 00081607 |
| Permit Number |
00081607 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO CUT SHEETS PROVIDED FOR FIRE | | | SPRINKLER HEADS PLANNED FOR USE. | | | PLEASE PROVIDE CUT SHEETS FOR FIRE | | | SPRINKLER HEADS THAT WILL BE USED | | | INSIDE THE BUILDING. | | | 2) ENTIRE FIRE SPRINKLER AND STANDPIPE | | | SYSTEM IS SUBJECT TO FIRE RESCUE | | | APPROVAL. | | | 3) SOFFITS ARE NOT TO INTERFERE WITH | | | ANY FIRE SPRINKLER HEAD DISCHARGE | | | PATTERNS. | | | 4) FIRE DEPARTMENT CONNECTION TO BE | | | NO MORE THAN 150 FEET TO A FIRE | | | HYDRANT. | | | APPROVED PROVISO: |
|