| Plan Review Notes For Permit 00081560 |
| Permit Number |
00081560 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) SMOKE DETECTORS TO BE INSTALLED A | | | MINIMUM OF THREE FEET FROM AIR | | | CONDITIONER DIFFUSERS. | | | 2) WHEN ACTIVATED, THE FIRE ALARM SYSTEM | | | IS TO BE AUDIBLE THROUGHOUT. | | | 3) IF BUILDING IS FIRE SPRINKLER | | | PROTECTED, THEN FLOW AND TAMPER | | | SWITCHES ARE TO BE SUPERVISED AND BE | | | MONITORED. |
|