| Plan Review Notes For Permit 00081536 |
| Permit Number |
00081536 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION | | | LOCATED ON THE NORTH SIDE OF THE | | | BUILDING WILL BE BLOCKED BY A SECURITY | | | FENCE LOCATED AT THE SERVICE ROAD AND | | | THE EAST VEHICLE ENTRY POINT. PLEASE | | | RELOCATE THIS DEVICE SO THAT IT COULD | | | BE USED BY FIRE RESCUE IN AN EMERGENCY. | | | 2) GARAGE DOORS WHEN OPENED ARE NOT TO | | | INTERFERE WITH FIRE SPRINKLER OPERATION | | | IN THE GARAGES. | | | 3) FIRE SPRINKLERS CANNOT BE OMITTED | | | FROM ENTRY FOYER IF THAT IS THE ONLY | | | MEANS OF EGRESS. | | | 4) SOFFITS ARE NOT TO INTERFERE WITH | | | FIRE SPRINKLER HEAD DISCHARGE. | | | 5) TOWNHOUSE UNITS ARE TO BE SEPARATED | | | FROM ONE ANOTHER BY AT LEAST TWO HOUR | | | FIRE WALLS. | | | APPROVED PROVISO: |
|