Plan Review Notes
Plan Review Notes For Permit 00081531
Permit Number 00081531
Review Stop FS
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) THE FIRE DEPARTMENT CONNECTION
 LOCATED ON THE NORTH SIDE OF THE
 BUILDING WILL BE LOCATED AT THE
 SERVICE ROAD AND THE EAST VEHICLE ENTRY
 POINT. PLEASE RELOCATE THIS DEVICE SO
 THAT IT COULD BE USED IN AN EMERGENCY
 BY FIRE RESCUE.
 2) GARAGE DOORS WHEN OPENED ARE NOT TO
 INTERFERE WITH FIRE SPRINKLER OPERATION
 IN THE GARAGES.
 3) FIRE SPRINKLERS CANNOT BE OMITTED
 FROM ENTRY FOYER IF THAT IS THE ONLY
 MEANS OF EGRESS.
 4) SOFFITS ARE NOT TO INTERFERE WITH
 FIRE SPRINKLER HEAD DISCHARGE.
 5) TOWNHOUSE UNITS ARE TO BE SEPARATED
 FROM ONE ANOTHER BY AT LEAST TWO HOUR
 FIRE WALLS.
 APPROVED PROVISO: