| Plan Review Notes For Permit 00081384 |
| Permit Number |
00081384 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE PROVIDE LAYOUT OF ALL | | | AREAS PERTAINING TO ART 500 AND ART; | | | 514. | | | | | | 2)NOTE: PLEASE SEE 384-16-D FOR MAX LOAD | | | FOR OCP. SEE E-2 FOR PANEL LOADS SHOWN. | | | | | | 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125% ON LOAD ANALYSIS. | | | | | | 4)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BLDG.STRUC. STEEL PER 250-50 | | | | | | | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | | | | 561-659-8096 EXT 8372 |
|