2001-01-08 00:00:00DENIED
  
 1)EXTRA FACE PAGE OF THE ENERGY SHEET
 REQUIRED.
  
 2)FRAMING NOTE 14 CALLS FOR D.W. SCREWS
 TO BE 12"O.C. TABLE 2306.1 CALLS FOR 8"
 O.C. PLEASE RECHECK.
  
 3)FIXED BUTT GLASS MUST COMPLY WITH SEC.
 2406.2
  
 4)PRODUCT APPROVAL FOR ROOF IS REQUIRED.
  
 5)THE DESIGN CERTIFICATION SHOWS A MEAN
 ROOF HEIGHT OF 15 FT.,THE ACTUAL M.R.H.
 IS 19'3".PLEASE RECHECK AS THE PRESSURE
 (T1606.2A)IS DIFFERENT.
  
 6)PROVIDE SOIL COMPACTION TEST RESULTS
 AT FIRST INSPECTION.
  
 7)PALM BEACH COUNTY IMPACT FEES MUST BE
 PAID,PLANS STAMPED BY THEM AND COPY OF
 RECEIPT SUBMITTED TO CITY OF WPB BLDG.
 DEPT. BEFORE A PERMIT TO CONSTRUCT WILL
 BE ISSUED.