Plan Review Notes
Plan Review Notes For Permit 00081305
Permit Number 00081305
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT/MAINS/PANELS ETC. PER-
 110-9/215-5
  
 2)NOTE: PLEASE NOTE THAT SD DETECTORS
 ARE MISSING INSIDE AND OUTSIDE BEDROOM.
 NFPA-72 2-2.1.1.1
  
 3)NOTE; MISSING OUTLET FRONT OF DWELLING
 PER 210-52E
  
 4)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3
  
 5)NOTE: PLEASE SHOW EQUIPMENT GROUNDING
 CONDUCTOR PER 250-122 BETWEEN DISCONNECT
 AND PANEL.
  
 6)NOTE: PLEASE SHOW MAIN DISCONNECT FROM
 RISER DIAGRAM ON ELECTRICAL PLAN NEXT
 TO METER. NOTE;110-26
  
 7)NOTE: PLEASE PLACE ELECTRICAL RISER,
 PANEL SCHEDULE, CALCULATIONS ON E-SHEET
 WITH ELECTRICAL FLOOR PLAN.215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372