Plan Review Notes
Plan Review Notes For Permit 00081302
Permit Number 00081302
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED PER TONY MARCELLO 9-25-00 RLM
  
 DENIED
  
  
 1)DESIGN CERTIFICATE SHEET INDICATES A
 M.R.H. OF 15',THE ACTUAL M.R.H.IS 18'.
 THE BASIC V.P. IS DIFFERENT (T16062A)
 PLEASE RECHECK.
  
 2)PLEASE SUPPLY AN EXTRA ENERGY FACE
 PAGE.
  
 3)THE BUTT GLASS IN THE LIVING ROOM MUST
 COMPLY WITH SEC.2406.2.
  
 4)PRODUCT APPROVAL IS REQUIRED FOR THE
 ENTRY DOOR.
  
 5)PRODUCT APPROVAL IS REQUIRED FOR THE
 GARAGE DOOR, THE GARAGE SIDE ENTRY AND
 THE FOYER ENTRY.