| Plan Review Notes For Permit 00081302 |
| Permit Number |
00081302 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | DENIED PER TONY MARCELLO 9-25-00 RLM | | | | | | DENIED | | | | | | | | | 1)DESIGN CERTIFICATE SHEET INDICATES A | | | M.R.H. OF 15',THE ACTUAL M.R.H.IS 18'. | | | THE BASIC V.P. IS DIFFERENT (T16062A) | | | PLEASE RECHECK. | | | | | | 2)PLEASE SUPPLY AN EXTRA ENERGY FACE | | | PAGE. | | | | | | 3)THE BUTT GLASS IN THE LIVING ROOM MUST | | | COMPLY WITH SEC.2406.2. | | | | | | 4)PRODUCT APPROVAL IS REQUIRED FOR THE | | | ENTRY DOOR. | | | | | | 5)PRODUCT APPROVAL IS REQUIRED FOR THE | | | GARAGE DOOR, THE GARAGE SIDE ENTRY AND | | | THE FOYER ENTRY. |
|