Plan Review Notes
Plan Review Notes For Permit 00081302
Permit Number 00081302
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE:PLEASE SUBMIT AIC RATINGS FOR ALL
 EQUIPMENT BEING INSTALLED. MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT PER
 110-9. 215-5 THIS IS REQ`D ON ALL PLANS.
  
 2)NOTE: PLEASE SHOW EQUIPMENT GRND REQ`D
 BETWEEN MAIN DISC AND PANEL. 250-122
  
 3)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3ON PANEL
 SCHEDULE. 215-5
  
 4)NOTE: PLEASE SHOW MAIN DISCONNECT ON
 HOUSE PLANS WITH METER.NOTE. 110-26
  
 5)NOTE: MISSING GFI/REC PER 210-52E
  
 6)NOTE: PLEASE SEE 210-70 FOR EGRESS
 LIGHTING FROM GARAGE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMAITON
 FOR REVIEW. ALSO PLEASE PLACE ELECTRICAL
 RISER/CALCULATIONS/PANEL SCHEDULE ON
 E-SHEET WITH ELECTRICAL FLOOR PLANS.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372