| Date |
Text |
| 2001-01-08 00:00:00 | 1) THIS REVIEW WAS PERFORMED ON THE |
| | FIRST FLOOR EXIT HALLWAY AND SERVICE |
| | AREAS. IT WAS NOTED THAT NO FIRE ALARM |
| | DEVICES HAVE BEEN SHOWN IN THE |
| | RESTAURANT, PERFORMANCE HALL, |
| | UNDERGROUND MECHANICAL ROOM, OR TENANT |
| | SPACES. WRITER CONTACTED FRED GRINER |
| | OF CITY PLACE WHO ADVISED THAT THIS |
| | REVIEW IS ONLY FOR THE FIRST FLOOR. |
| | ADDITIONAL DEVICES WILL BE INSTALLED |
| | IN THE OTHER AREAS UNDER SEPARATE |
| | PLANS AND PERMITS. IT WAS AGREED BY |
| | FRED GRINER AND THIS WRITER THAT WHEN |
| | THE PERFORMANCE HALL IS FITTED UP THAT |
| | THE FIRE ALARM SYSTEM WILL BE CONVERTED |
| | TO VOICE EVACUATION TAPED MESSAGE. |
| | 2) NO CUT SHEETS PROVIDED FOR DEVICES |
| | SHOWN ON PLANS. |
| | 3) FIRE ALARM SYSTEM TO BE MONITORED BY |
| | A UL LISTED CENTRAL STATION APPROVED |
| | BY THE FIRE RESCUE DEPARTMENT. THE |
| | FOLLOWING SIGNALS ARE TO BE RECEIVED |
| | AT THE CENTRAL STATION, WATERFLOW, |
| | GENERAL ALARM, SUPERVISORY, TROUBLE. |
| | APPROVED PROVISO: |
| | ON AUGUST 25, 2000, WRITER WAS FAXED |
| | CUT SHEETS ON DEVICES PLANNED FOR |
| | USE. |