| 2001-01-08 00:00:00 | 1)ACCESSIBLE TOILET ROOMS LOCATED IN |
| | STORAGE AREAS SHALL BE INDELIBLY POSTED |
| | FOR THE INTENDED USE,BE ON AN ACCESSIBLE |
| | ROUTE AND AVAILABLE TO PATRONS WITHOUT |
| | RESTRTICTION DURING NORMAL OPERATING |
| | HOURS.THE ACCESSIBLE ROUTE SHALL BE |
| | CLEARLY DEFINED ON THE PLANS. |
| | FLA.ACCESSIBILITY CODE SECS.4.1,4.2,4.3. |
| | STANDARD PLUMBING CODE SEC.407.2.2. |
| | |
| | 2)INDICATE COMPLIANCE W/COMMENT #1 ON |
| | THE PLANS. |
| | |
| | 3)INSTANT WATER HEATERS SHALL NOT |
| | INFRINGE UPON THE REQUIRED CLEARANCES |
| | PER FACBC SEC.4.19,FIGS.31 & 32. |
| | PLUMBING PLANS EXAMINER. |
| | |
| | 4)ONLY 2 FIXTURES PERMITTED ON 1/2"C.W. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.607.7 |
| | |
| | 5)LAVS SHALL CONNECT TO THE STACK W/O |
| | OFFSETS.SPC SEC.1001.5,1001.9. |
| | |
| | 6)FLOOR DRAINS ARE REQD.IN THE TOILET |
| | ROOMS PER SPC SEC.409.4.1.1. |
| | |
| | 7)FLOORS AND WALLS SHALL BE NONABSORBENT |
| | TO A HEIGHT OF 4'PER SBC SEC.1204.2. |
| | |
| | 8)DRINKING FOUNTAIN SHALL COMPLY W/FACBC |
| | 4.1.3(10)(A)PROVISIONS SHALL BE MADE FOR |
| | PEOPLE WHO HAVE TROUBLE BENDING OR |
| | STOOPING. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |