Plan Review Notes
Plan Review Notes For Permit 00081286
Permit Number 00081286
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************DENIED********************
 1. PROVIDE OUTSIDE AIR SCHEDULE PER
 ASHRAE 62-89
 2. PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 1997 SMC 501.2
 3. SECONDARY DRAIN LINE SHALL NOT TIE
 INTO PRIMARY DRAIN LINE. RUN SEPARATELY
 AND TERMINATE IN A CONSPICOUS LOCATION
 OR USE FLOAT SWITCH PER 1997 SMC 304.8
 4. FAN SHUT DOWN BY DUCT SMOKE DETECTOR
 REQUIRED/TIED TO BUILDING FIRE ALARM
 PER NFPA 90A 4-4.4