| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1. PROVIDE OUTSIDE AIR SCHEDULE PER | | | ASHRAE 62-89 | | | 2. PROVIDE AIR BALANCE SCHEDULE SHOWING | | | COMPLIANCE WITH 1997 SMC 501.2 | | | 3. SECONDARY DRAIN LINE SHALL NOT TIE | | | INTO PRIMARY DRAIN LINE. RUN SEPARATELY | | | AND TERMINATE IN A CONSPICOUS LOCATION | | | OR USE FLOAT SWITCH PER 1997 SMC 304.8 | | | 4. FAN SHUT DOWN BY DUCT SMOKE DETECTOR | | | REQUIRED/TIED TO BUILDING FIRE ALARM | | | PER NFPA 90A 4-4.4 |
|