| Plan Review Notes For Permit 00081286 |
| Permit Number |
00081286 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) WRONG LIFE SAFETY CODE REFERENCED. | | | SHOULD READ NFPA 101, 1985 LIFE SAFETY | | | CODE INSTEAD OF NFPA 101, 1991 LIFE | | | SAFETY CODE. | | | 2) PROVIDE FIRE ALARM DRAWINGS FOR FIRE | | | ALARM EQUIPMENT SHOWN ON PLANS. A | | | SEPARATE PLAN AND PERMIT REQUIRED. CUT | | | SHEETS REQUIRED ON ALL DEVICES PLANNED | | | FOR USE. | | | 3) FINISH SCHEDULE DOES NOT INDICATE | | | FLAME SPREAD RATING FOR WALLS AND | | | CEILINGS. INTERIOR FINISH IN MERCANTILE | | | OCCUPANCIES SHALL BE CLASS A OR B. | | | 4) PROVIDE FIRE SPRINKLER SHOP DRAWINGS | | | WITH PERMIT FOR FIRE SPRINKLER SYSTEM | | | INSTALLATION. | | | 5) EXITING PERMITTED THROUGH STOCKROOM | | | IF THE FOLLOWING CONDITIONS EXIST: | | | STOCKROOM DOOR FROM SALES AREA CANNOT | | | BE SUBJECT TO LOCKING, NOT MORE THAN | | | 50 PERCENT OF EXIT ACCESS CAN BE THROUGH | | | STOCKROOM, A 44" AISLE IS TO BE PROVIDED | | | AND MAINTAINED. |
|