| Plan Review Notes For Permit 00081273 |
| Permit Number |
00081273 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PLEASE PROVIDE SPARE HEAD BOX AND | | | WRENCH IN ACCORDANCE WITH NFPA 13. | | | 2) FIRE SPRINKLER SYSTEM TO BE | | | SUPERVISED IN ACCORDANCE WITH FIRE AND | | | BUILDING CODE REQUIREMENTS. | | | 3) SYSTEM TO BE PRESSURE TESTED AT 200 | | | POUNDS FOR TWO HOURS AS PER NFPA 13. |
|