| Plan Review Notes For Permit 00081261 |
| Permit Number |
00081261 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE ELECTRICAL CHANGES | | | HANDWRITTEN ON PLANS. THEY DON`T APPEAR | | | TO HAVE THE SAME SIGNATURE AS ENGINEER | | | OF RECORD?? PLEASE CALRIFY. | | | | | | 2)NOTE: PLEASE NOTE, SMOKE DETECTORS ARE | | | REQ`D INSIDE AND OUTSIDE SLEEPING ROOMS | | | NFPA-72 2-2.1.1.1. | | | | | | 3)NOTE: PLEASE SEE 210-11-C-3 FOR THE | | | REQ`D BATH(S) CIRCUIT(S).20A/#12. | | | PLEASE INCLUDE ON PANEL SCHEDULE. | | | | | | 4)NOTE: ARE THERE GOING TO BE ANY CATV, | | | OR TELEPHONE OUTLETS IN BEDROOM? IF SO, | | | PLEASE SHOW ON PLANS.215-5 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THER ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-659-8096 EXT 8372 |
|