Plan Review Notes
Plan Review Notes For Permit 00081261
Permit Number 00081261
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE SEE ELECTRICAL CHANGES
 HANDWRITTEN ON PLANS. THEY DON`T APPEAR
 TO HAVE THE SAME SIGNATURE AS ENGINEER
 OF RECORD?? PLEASE CALRIFY.
  
 2)NOTE: PLEASE NOTE, SMOKE DETECTORS ARE
 REQ`D INSIDE AND OUTSIDE SLEEPING ROOMS
 NFPA-72 2-2.1.1.1.
  
 3)NOTE: PLEASE SEE 210-11-C-3 FOR THE
 REQ`D BATH(S) CIRCUIT(S).20A/#12.
 PLEASE INCLUDE ON PANEL SCHEDULE.
  
 4)NOTE: ARE THERE GOING TO BE ANY CATV,
 OR TELEPHONE OUTLETS IN BEDROOM? IF SO,
 PLEASE SHOW ON PLANS.215-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THER ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-659-8096 EXT 8372