| 2001-01-08 00:00:00 | ******************PROVISO*************** | | | 1)VEG.SINK NOT SHOWN ON SANITARY RISER. | | | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 | | | | | | 2)MAX.OF 4 FIXTURE UNITS PERMITTED ON 2" | | | WET VENT.SEE M.B.STACK. | | | | | | 3)SHOWER IN M.B.SHALL CONNECT TO HORIZ. | | | DRAIN DOWNSTREAM OF W.C.PER COUNTYWIDE | | | AMENDMENTS TO SPC SEC.911.1.1. | | | | | | 4)SUBMIT REVISED SIGNED,DATED AND SEALED | | | SANITARY RISER PRIOR TO PLUMBING INSP. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | | ANY QUESTIONS. | | | TIMOTHY LARGE | | | PLUMBING PLANS EXAMINER. |
|