Plan Review Notes
Plan Review Notes For Permit 00081234
Permit Number 00081234
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00******************PROVISO***************
 1)VEG.SINK NOT SHOWN ON SANITARY RISER.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 2)MAX.OF 4 FIXTURE UNITS PERMITTED ON 2"
 WET VENT.SEE M.B.STACK.
  
 3)SHOWER IN M.B.SHALL CONNECT TO HORIZ.
 DRAIN DOWNSTREAM OF W.C.PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.911.1.1.
  
 4)SUBMIT REVISED SIGNED,DATED AND SEALED
 SANITARY RISER PRIOR TO PLUMBING INSP.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.