| Plan Review Notes For Permit 00081234 |
| Permit Number |
00081234 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT COMPLETED PLANS. | | | NO RISER DIAGRAM/LOAD CALCULATIONS/ | | | PANEL SCHEDULES????????? | | | | | | 2)NOTE: MISSING SMOKE DETECTORS FOR | | | MEDIA/PLAY ROOM.ROOMS WITH BATHS AND OR | | | CLOSETS ARE ADAPTABLE TO SLEEPING ROOMS | | | AND THEREFORE REQ` SMOKE DETECTORS PER | | | NFPA-72. | | | | | | 3)NOTE; MISSING WP GFI FOR A/C CU ON | | | MASTER BATH SIDE OF HOUSE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561-659-8096 EXT 8372 | | | | | | **PLEASE SEE MISSING OUTLETS PER 210-52 | | | BEDROOM #4 |
|