| Plan Review Notes For Permit 00081232 |
| Permit Number |
00081232 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-01-22 00:00:00 | THE STAIR SHOP DRAWINGS BY AA GARGIULO | | | DATED 1/12/01 DO NOT COMPLY WITH SBC | | | 1015.2 AND SBC 1015.3 GUARD RAILS, AS | | | TO HEIGHT AND RAIL INTERMEDIATE SPACING. | | | | | | ALSO, THE 7 - 11 RISE RUN RATIO WILL NOT | | | WORK IN THE 9' - 6" RUN SHOWN FOR THE | | | FLIGHT.PLEASE REVISE AS NECESSARY. | | | | | | HAROLD PISKURA PLAN REVIEW |
|