| Plan Review Notes For Permit 00081232 |
| Permit Number |
00081232 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-03-01 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS ARE NOW | | | COMING IN SHOWING NEW SERVICE? | | | PLEASE NOTE THAT THE VALUE ON PERMIT | | | APPLICATION FOR ELECTRICAL MUST BE | | | INCREASED TO ACCOMADATE. | | | | | | 2)NOTE: PLEASE NOTE THERE IS NOT ENOUGH | | | INFORMATION FOR REVIEW OF NEW SERVICE. | | | PLEASE SUBMIT A ONE LINE DIAGRAM/ ELEC | | | RISER DIAGRAM. NEED ALOT MORE DETAIL ON | | | EQUIPMENT. WIRE SIZES/CONDUIT SIZES | | | ECT ECT.PANEL SCHEDULES? | | | | | | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 4)NOTE: PLEASE NOTE LIGHT FIXTURE IN | | | CLOSET | | | NOT PERMITTED AS SHOWN PER 410-8. | | | | | | 5)NOTE: PLEASE SHOW ALL BRANCH CIRCUIT | | | #`S ON PLANS THAT CORRELATE WITH PANEL | | | SCHEDULS.215-5 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|