| 2001-01-08 00:00:00 | BUILDING PLAN REVIEW: |
| | 1:HANDICAPPED ACCESSABLE ROOMS BUILD "B" |
| | SHEET A4: FLORIDA ACCESSABLITY CODE |
| | A:9.1.3 SLEEPING ACCOMMODATIONS FOR |
| | PERSONS WITH HEARING IMPAIRMENTS SHALL |
| | COMPLY WITH 9.3 VISUAL ALARMS, NOTIF- |
| | ICATION DEVICES & TELEPHONES. |
| | B:9.1.5 IN ADDITION TO THE REQUIRED |
| | SLEEPING ROOMS REQUIRED 9.1.5 REQUIRES |
| | AT LEAST ONE SLEEPING ROOM OR SUITE |
| | THAT COMPLIES WITH THE REQIUREMENTS OF |
| | 9.3 VISUAL ALARMS,NOTIFICATION DEVISES |
| | & TELEPHONES. |
| | C:4.13.5 DOORS/CLEAR WIDTH: DOORWAYS |
| | SHALL HAVE A CLEAR OPENING OF 32" WITH |
| | THE DOOR OPEN 90 DEGREES, MEASURED |
| | BETWEEN THE FACE OF THE DOOR AND THE |
| | OPPOSITE STOP. |
| | D:4.13.6 DOORS MANEUVERING CLEARENCES AT |
| | DOORS.MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE SHOWN IN FIG. |
| | 25. THE FLOOR OR GROUND AREA WITHIN |
| | THE REQUIRED CLEARENCES SHALL BE LEVEL |
| | AND CLEAR. |
| | E:9.2.2REQUIREMENTS FOR ACCESIBLE UNITS, |
| | SLEEPING ROOMS AND SUITES.MINIMUM |
| | REQUIREMENTS:AN ACCESIBLE UNIT SHALL |
| | BE ON AN ACCESIBLEROUTE COMPLYING |
| | WITH 4.3, SHOW ON THE FLOOR PLAN THE |
| | ELEMENTS (BED, CABINETS,DRAWER SPACE |
| | CLOSETS & TELEPHONES). |
| | 2:BEVERAGE AREA : 5.2 COUNTERS & BARS; |
| | WHERE FOOD OR DRINK IS SERVED AT |
| | COUNTERS EXCEEDING 34" IN HEIGTH FOR |
| | CONSUMPTION BY THE CUSTOMERS SEATED ON |
| | STOOLS OR STANDING AT TTHE COUNTER, A |
| | PORTION OF THE MAIN COUNTER WHIICH IS |
| | 60" IN LENGTH MINIMUM SHALLBE PROVIDED |
| | IN COMPLIANCE WITH 4.32OR SERVICE |
| | SHALL BE AVAILABLE AT ACCESSIBLE TABLE |
| | WITH IN THE SAME AREA. |
| | 3:LOBBY TELEPHONE TO COMPLY WITH FL. ACC |
| | CODE 4.31 TELEEPHONES. |
| | 4:LOBBY DOORS CLOUDED AREA: SHALL COMPLY |
| | WITH FL ACC CODE 4.13.5 CLEAR WIDTH OF |
| | 32".PLAN CALLS FOR2'-8" DOOR (2). |
| | NONCOMPLIANCE. |
| | 5:LOBBY DOORS AND GLAZED OPENING. SBC |
| | 2405.2 SAFETY GLASS REQUIRED. |
| | 6:SBC 1006.2.4 EXTERIOR STAIRS SHALL BE |
| | SEPERATED FROM THE INTERIOR OF THE |
| | BUILDING BY WALLS WITH A FIRE RESIS- |
| | TANCE RATING OF NOT LESS THAN 1 HR. |
| | WITH FIXED OR SELF CLOSING OPENING PRO |
| | TECTIVES AS REQUIRED FOR ENCLOSED |
| | STAIRS. THIS PROTECTION SHALL EXTEND |
| | VERTICALLY FROM THE GROUND TO A POINT |
| | 10 FT ABOVE THE TOPMOST LANDING OR THE |
| | ROOF LINE, WHICHEVER IS LOWER, AND |
| | HORIZONTALLY 10 FT FROM EACH SIDE OF |
| | THE STAIRWAY. OPENINGS WITHIN THE 10 |
| | FT HORIZONTAL EXTENSION OF THE PRO- |
| | TECTED WALLS BEYOND THE STAIRWAY SHALL |
| | BE EQUIPPED WITH FIXED 3/4-HOUR |
| | ASSEMBLIES. THE GAS HEATER /METER MUST |
| | NOT BE LOCATED BENEATH THE STAIRWELL. |
| | 7:STANDARD BUILD CODE:1606.4/1707.4.1 |
| | W.P.B. AMENDMENTS-EXTERIOR WINDOWS AND |
| | DODR ASEMBLIES REPLACED WILL REQUIRE |
| | PRODUCT APPROVAL REPORTS(2) FOR IMPACT |
| | FROM WIND BORN DEBRIS, LARGE MISSLE |
| | IMPACT TESTING. GLAZED OPENINGS THAT |
| | DO NOT MEET THIS TESTING WILL NEED |
| | TESTED SHUTTERS THAT DO HAVE APPROVED |
| | TESTING AND ACCOMPINING REPORTS. WE |
| | ACCEPT DADE COUNTY PRODUCT APP. OR |
| | S.B.C.C.I. REPORT. |
| | WE WILL ALSO NEED INFORMATION ON THE |
| | 1-HR RAED WINDOW, AND ON THE 2ND FL |
| | DOOR AS WELL AS THE 1ST FLOOR DOOR |
| | DIRECTLY BELOW THE 2ND FLOOR LANDING. |
| | 8:104.2.2: ON THE 2ND FLOOR PLAN THERE |
| | IS A BEDROOM THAT HAS NO MEANS OF |
| | EGRESS NOR DOES IT SHOW THE WINDOW, |
| | THIS MAY ALSO REQUIRE A 1-HR FIRE |
| | RATING IF LOCATED ON THE WALL OF THE |
| | EXTERIOR STAIRS. |
| | 9:104.2.2: THE PLANS DO NOT SHOW WHERE |
| | THE HANDICAPPED PARKING AND PASSENGER |
| | LOADING ZONES WILL BE? |
| | |
| | BUILDING PLAN REVIEW: |
| | JIM WITMER |
| | (561) 659-8096 EX 8412 |
| | NOTES: |
| | IF YOU HAVE ANY QUESTIONS,PLEASE CALL. |
| | PLEASE RETURN THE REVIEWED PAGES WITH |
| | THE CORRECTIONS IN ORDER TO EXPEDITE THE |
| | REVIEW PROCESS.THANK YOU! |