Plan Review Notes
Plan Review Notes For Permit 00081220
Permit Number 00081220
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)THE OCCUPANT LOAD SHALL BE BASED ON
 THE SQ.FOOT AREA OF HABITABLE FLOOR
 SPACE.SEE SPC SEC.407.1.3 FOR ALLOWED
 DEDUCTIBLE AREAS.YOU MUST SUBMIT THE
 SQ.FEET OF THE AREAS,THE SQ.FEET OF EACH
 AREA BEING DEDUCTED,AND THE FINAL RESULT
 FOR EACH APPLICABLE OCCUPANCY TYPE.
 COMPLY W/SPC TABLE 407 FOR MIN.FIXTURE
 REQS.AS DESIGNED THERE ARE INSUFFICIENT
 FIXTURES.
  
 2)SHT.A301R-THE DOOR ON THE HANDICAP
 STALL IN THE MEN'S RESTROOM CANNOT
 SWING INTO THE CLEAR FLOOR SPACE FOR THE
 URINAL PER FACBC SEC.4.17.5.
  
 3)A CLEAR FLOOR SPACE MIN.OF 30"WIDE
 IS REQD.AT THE URINAL PER FACBC SEC.
 4.18.3.
  
 CALL IF YOU HAVE QUESTIONS.
 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.