| 2001-01-08 00:00:00 | 1)SUBMIT OCCUPANT LOAD FOR THIS AREA PER |
| | SPC TABLE 407.SEE SPC 407.1.3.FOR |
| | ALLOWED DEDUCTIBLE AREAS. |
| | |
| | 2)SUBMIT ENLARGED FLOOR PLAN THAT |
| | CLEARLY SHOWS THE DIMENSIONS(LXW)OF THE |
| | ACCESSIBLE STALLS,STANDARD STALLS, |
| | FIXTURE CLEARANCES,ETC.COUNTYWIDE AMEND- |
| | MENTS TO SPC SEC.104.2.1.,FACBC SEC. |
| | 4.17.3. |
| | |
| | 3)SUBMIT DETAILS FOR MOUNTING HEIGHTS/ |
| | DIMENSIONS OF ALL HANDICAP FIXTURES AND |
| | APPURTENANCES.COUNTYWIDE AMENDMENTS TO |
| | SPC SEC.104.2.1. |
| | |
| | 4)DRINKING FOUNTAIN SHALL COMPLY W/FACBC |
| | SEC.4.1.3.(10)(A).PROVISIONS SHALL BE |
| | MADE FOR PEOPLE WHO HAVE TROUBLE BENDING |
| | OR STOOPING. |
| | |
| | 5)MINIMUM NUMBER OF REQD.PLUMBING |
| | FIXTURES SHALL COMPLY W/SPC TABLE 407. |
| | |
| | 6)SHT.P104-CONDENSATE DRAIN CANNOT DRAIN |
| | INTO DOWNSPOUT OR ROOF DRAIN.DRAIN SHALL |
| | BE RUN INDEPENDENT TO CATCH BASIN OR |
| | DRY WELL.SMC SEC.304.8.3. |
| | |
| | 7)SHTS.P103,104-REFERS TO CIVIL DRAWINGS |
| | FOR CONTINUATION OF STORM DRAIN LINES. |
| | THESE LINES ARE NOT SHOWN ON THE CIVILS. |
| | COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1 |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |