2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD FOR THIS AREA PER
 SPC TABLE 407.SEE SPC 407.1.3.FOR
 ALLOWED DEDUCTIBLE AREAS.
  
 2)SUBMIT ENLARGED FLOOR PLAN THAT
 CLEARLY SHOWS THE DIMENSIONS(LXW)OF THE
 ACCESSIBLE STALLS,STANDARD STALLS,
 FIXTURE CLEARANCES,ETC.COUNTYWIDE AMEND-
 MENTS TO SPC SEC.104.2.1.,FACBC SEC.
 4.17.3.
  
 3)SUBMIT DETAILS FOR MOUNTING HEIGHTS/
 DIMENSIONS OF ALL HANDICAP FIXTURES AND
 APPURTENANCES.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 4)DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 5)MINIMUM NUMBER OF REQD.PLUMBING
 FIXTURES SHALL COMPLY W/SPC TABLE 407.
  
 6)SHT.P104-CONDENSATE DRAIN CANNOT DRAIN
 INTO DOWNSPOUT OR ROOF DRAIN.DRAIN SHALL
 BE RUN INDEPENDENT TO CATCH BASIN OR
 DRY WELL.SMC SEC.304.8.3.
  
 7)SHTS.P103,104-REFERS TO CIVIL DRAWINGS
 FOR CONTINUATION OF STORM DRAIN LINES.
 THESE LINES ARE NOT SHOWN ON THE CIVILS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.