2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS OR
 HYDRAULIC CALCULATIONS PROVIDED WITH
 PLANS. THE PLANS INDICATE THE BUILDING
 WILL BE COMPLETELY FIRE SPRINKLER
 PROTECTED. PLEASE SUBMIT THIS
 INFORMATION WITH PLANS.
 2) PLEASE EXPLAIN HOW FIRE RESCUE WILL
 ENTER THE SECURITY GATES.
 3) NO BUILDING ADDRESS LOCATED ON
 ELEVATION DRAWINGS.
 4) PLEASE PROVIDE A LIFE SAFETY PLAN TO
 THIS OFFICE FOR REVIEW.
 5) PLEASE INDICATE SAFETY MEASURES FOR
 DISPAY OF VEHICLES WITHIN BUILDING.