2001-01-08 00:00:00FAILED
  
  
  
 GENERAL NOTE:
  
 1.AN APPROVED BACKFLOW PREVENTER,
 ASSEMBLY WILL NEED TO BE INSTALLED,
 IF NOT ALREADY IN PLACE, AT THE POINT,
 OF SERVICE ON PRIVATE PROPERTY. ALL,
 BACKFLOW PREVENTERS SHALL BE COMPLETELY,
 HIDDEN FROM VIEW WITH SHRUBS PRIOR TO,
 ACTIVATION.
  
 2.A CLEAN-OUT WILL NEED TO BE INSTALLED,
 IN THE SANITARY SEWER LATERAL, ON THE,
 PROPERTY AT THE BACK OF THE SIDEWALK,
 IF NOT ALREADY INSTALLED.
  
 3.A SEPARATE IRRIGATION METER IS
 SUGGESTED TO SAVE ON THE MONTHLY
 WATER BILL. AN APPROVED BACKFLOW
 PREVENTER WILL NEED TO BE INSTALLED
 ON THIS LINE.
  
 4.IF KITCHEN FACILITIES OR WORK SHOPS
 ARE BUILT THEN OIL AND OR GREASE
 SEPARATORS WILL NEED TO BE INSTALLED
 TO MEET THE CITIES WASTEWATER DISCHARGE
 ORDINANCE.
  
 5.NO TREES SHALL BE PLANTED WITHIN 5'
 OF ANY WATER, SANITARY OR STORM LINE
 OWNED BY THE CITY OF WEST PALM BEACH.
 NO TREES SHALL BE PLANTED IN ANY
 UTILITIES EASEMENT THAT HAVE OUR WATER,
 SANITARY OR STORM LINES IN THEM.
 THE 5' CLEARANCE SHALL MEAN FROM
 THE OUTSIDE OF THE UTILITY LINE TO
 THE EDGE OF THE ROOT BALL OF THE TREE.
 IF THESE CLEARANCES CAN NOT BE MET
 THEN ROOT BARRIER MATERIAL MAY BE USED,
 IF SUBMITTED ON AND APPROVED AT THE TIME
 OF THE PLAN REVIEW.NO PLANTS, TREES,
 LIGHT POLES, TRASH RECEPTACLES AND/OR
 SIGN POSTS SHALL BE PLACED WITHIN 5' OF
 ANY HYDRANTS, CLEAN-OUTS ORWATER METER
  
 6.THE CITY OF WEST PALM BEACH PUBLIC
 UTILITIES DEPARTMENT STILL REQUIRES THE
 REVIEW AND APPROVAL OF THE PLANS FOR THE
 ACTUAL SERVICE CONNECTIONS TO BE MADE, A
 THE OWNERS EXPENSE, WHEN THE LOT HAS BEE
 APPROVED AND IS DEVELOPED.THE APPLICAB
 CAPACITY CHARGES, INSTALLATION CHARGES,
 DEPOSITS AND OTHER NORMAL FEES CHARGED B
 THE UTILITIES DEPARTMENT SHALL BE ASSESS
 AT THE TIME OF REQUEST FOR PERMITS/REVIE
  
 7.NO WATER AND OR SANITARY LINES CAN BE
 LAID, IF PLANS ARE NOT SUBMITTED TO US,
 SEPARATELY AND PRIOR TO SUBMITTAL FOR A
 BUILDING PERMIT FROM BUILDING AND ZONING
 ANDSERVICE WILL NOT BE GRANTED.
 (TO US MEANS UTILITIES DEPT
 1000 45TH ST, WPB, FL 33407
 (561) 659 8040 ATTENTION MANNY GONZALEZ)
  
 SIDEWALK AND DRIVEWAY REQUIREMENTS:
  
 1.ALL BROKEN SIDEWALKS ALONG THE PROPERT
 ALL SIDES) MUST BE REPLACED.
  
 2.ALL GRADES FOR CITY SIDEWALKS WILL BE
 SET BY THE CITY SURVEY CREW, CALL 659-80
 AND ASK FOR ED RYAN TO SET UP AN
 APPOINTMENT.
  
 STATE IF GARBAGE IS TO BE PICKED UP BY
 CITY OR IF IT IS PRIVATE PICKUP, IF TO
 BE PICKED UP BY THE CITY THEN THE
 FOLLOWING REQUIREMENTS MUST BE MET:
  
 1.DUMPSTER MUST HAVE A MINIMUM OF 12'-6"
 OPENING BETWEEN THE GATE POSTS.
 (YOUR DOES NOT ON SHEET SP-102R AND 2OF6
 2.INTERIOR DIMENSIONS OF THE ENCLOSURE
 MUST BE A MINIMUM OF 12'-6" WIDE AND
 12' DEEP.A CONCRETE PARKING STOP BARS
 10' LONG MUST BE CENTERED (FROM GATES)
 AND INSTALLED 18" FROM THE BACK WALL.
 STEEL BARS WILL BE DRILLED THRU THE
 STOP BAR AND INTO THE INTERIOR FLOOR
 OF THE ENCLOSURE TO STOP THE STOP BAR
 FROM MOVING WHEN THE DUMPSTER IS SET
 INSIDE.3. IF TRUCK ENTERS THRU OKEE-
 CHOBBE THEN IT MUST CLEAR CANOPY.
 4.THE OPENING OF THE DUMPSTER ENCLOSURE
 MUST BE ANGLED SO THAT A 40' LONG TRUCK
 CAN ACCESS DUMPSTER.