Plan Review Notes
Plan Review Notes For Permit 00081220
Permit Number 00081220
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00BUILDING COMMENTS
 -------------------
  
 1] PLEASE SUPPLY TEST REPORTS FOR ALL
 EXTERIOR GLAZING,DOORS AND ROOF COVERS
 2] PROVIDE FIRE SPRINKLER LAYOUT.
 3] ROOF SLOPES SHALL BE MINIMUM 1/4"PER
 FOOT.
 4] WEST ELEVATION WALL SHALL NOT CONTAIN
 COMBUSTIBLES [PLYWOOD].
 5] SUBMIT SPECIFICATIONS FOR DURAFORM
 PANELS AT ICON TOWER.
 6] PROVIDE 18" MANUVERING CLEARENCE AT
 THE PULL SIDE OF DOOR 12A,SEE SECTION
 4.13.6,1997 FL.ACC.CODE.
  
  
  
  
  
  
 REVIEWED BY:
 LUIS MARTINEZ
 561-659-8096
 EXT. 8456