Plan Review Notes
Plan Review Notes For Permit 00081203
Permit Number 00081203
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)A DRINKING FOUNTAIN IS REQD. PER SPC
 TABLE 407.FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A).PROVISIONS SHALL BE
 MADE FOR PEOPLE WHO HAVE TROUBLE BENDING
 OR STOOPING.
  
 2)SUBMIT A WATER ISOMETRIC FOR REVIEW.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 3)CLEANOUTS ARE REQD.AND SHALL COMPLY W/
 SPC SEC.710.2.
  
 4)A MAIN VENT IS REQD.PER SPC SEC.904.3.
  
 5)CLARIFY FLOOR DRAIN.IF IT'S FOR THE
 TOILET ROOM,INSTALL ONE IN EACH TOILET
 ROOM.SPC 409.4.1.1.
  
 6)SHOW WHEELCHAIR TURNING SPACE IN
 TOILET ROOMS.FACBC SEC.4.2.3.
  
 7)SHOW LOCATION OF FUTURE SINK ON PLANS.
 IF LOCATED IN A BREAK/LOUNGE AREA THE
 SINK SHALL COMPLY W/FACBC SEC.4.24.1-
 4.24.7.
  
 8)WALLS IN TOILET ROOMS SHALL BE
 NONABSORBENT TO A HEIGHT OF 4' PER SBC
 SEC.1204.2(PLANS NOTE PAINT-WHAT TYPE?)
  
 9)WATER CLOSETS NOT PERMITTED ON WET
 VENTS PER COUNTYWIDE AMENDMENTS TO SPC
 SEC.911.1.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.