Plan Review Notes
Plan Review Notes For Permit 00081203
Permit Number 00081203
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00INSUFFICIENT MECHANICAL INFORMATION FOR
 REVIEW. PROVIDE INFORMATION ON DIFFUSERS
 OUTSIDE AIR PER ASHRAE 62-89, AIR
 BALANCE SHOWING COMPLIANCE W/ SMC 501.2,
 VENTILATION AND BATH EXHAUST REQUIRED TO
 COMPLY WITH ASHRAE 62-89 AND STANDARD
 CODES
 FAN SHUT DOWN BY DUCT SMOKE DETECTOR W/
 NOTIFICATION BY BLDG FIRE ALARM OR HORN
 AND STROBE REQUIRED PER NFPA 90A 4-4.4