| 2001-01-08 00:00:00 | INSUFFICIENT MECHANICAL INFORMATION FOR | | | REVIEW. PROVIDE INFORMATION ON DIFFUSERS | | | OUTSIDE AIR PER ASHRAE 62-89, AIR | | | BALANCE SHOWING COMPLIANCE W/ SMC 501.2, | | | VENTILATION AND BATH EXHAUST REQUIRED TO | | | COMPLY WITH ASHRAE 62-89 AND STANDARD | | | CODES | | | FAN SHUT DOWN BY DUCT SMOKE DETECTOR W/ | | | NOTIFICATION BY BLDG FIRE ALARM OR HORN | | | AND STROBE REQUIRED PER NFPA 90A 4-4.4 |
|