2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PLANS SHOWING
 ALL BRANCH CIRCUIT #`S ON PLANS.
 PLEASE CORRELATE #`S WITH PANEL SCHEDULE
 TO BE SUBMITTED WITH PLANS. 215-5
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL MAINS AND PANELS. EQUIPMENT MUST BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9
  
 3)NOTE : PLEASE SHOW GROUNDING ELECTRODE
 ATTACHMENTS PER 250 OF THE NEC.
  
 4)NOTE :PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  