| Plan Review Notes For Permit 00081182 |
| Permit Number |
00081182 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-03-20 00:00:00 | ******************PROVISO*************** | | | | | | MECHANICAL DRAWING M7.1, DETAIL 1-M2.1 | | | FOR THE HVAC EQUIPMENT ROOF CURB DETAIL | | | INDICATES 18" MINIMUM - IF THIS CURB IS | | | FOR A ROOF TOP PACKAGE UNIT IN WHICH | | | THE UNIT FITS OVER THE CURB IT IS NOT | | | REQUIRED TO BE 18".THE 18" MINIMUM | | | CLEARENCE IS FOR STANDS AS INDICATED ON | | | DRAWING M7.2, IN WHICH THE CONDENSERS | | | SIT ON TOP AND THE ROOF IS CONTINUOUS | | | UNDERNEATH, THEREFORE THE 18" CLEARENCE | | | IS REQUIRED. | | | REFERENCE - AMENDED 1997 SMC 304.2.5. | | | | | | AS PER 1997 SMC 609.1.1, THERE SHALL BE | | | NO COMBUSTIBLES ABOVE CEILING IN RETURN | | | AIR PLENUM. | | | | | | DRAWING M6.1 AIR BALANCE SCHEDULE WAS | | | NOT ADJUSTED TO REFLECT THE ADDITION OF | | | AHU-4. |
|