2001-03-20 00:00:00******************PROVISO***************
  
 MECHANICAL DRAWING M7.1, DETAIL 1-M2.1
 FOR THE HVAC EQUIPMENT ROOF CURB DETAIL
 INDICATES 18" MINIMUM - IF THIS CURB IS
 FOR A ROOF TOP PACKAGE UNIT IN WHICH
 THE UNIT FITS OVER THE CURB IT IS NOT
 REQUIRED TO BE 18".THE 18" MINIMUM
 CLEARENCE IS FOR STANDS AS INDICATED ON
 DRAWING M7.2, IN WHICH THE CONDENSERS
 SIT ON TOP AND THE ROOF IS CONTINUOUS
 UNDERNEATH, THEREFORE THE 18" CLEARENCE
 IS REQUIRED.
 REFERENCE - AMENDED 1997 SMC 304.2.5.
  
 AS PER 1997 SMC 609.1.1, THERE SHALL BE
 NO COMBUSTIBLES ABOVE CEILING IN RETURN
 AIR PLENUM.
  
 DRAWING M6.1 AIR BALANCE SCHEDULE WAS
 NOT ADJUSTED TO REFLECT THE ADDITION OF
 AHU-4.