| Plan Review Notes For Permit 00081182 |
| Permit Number |
00081182 |
|
| Review Stop |
FIRE |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2001-03-14 00:00:00 | 1) THE MECHANICAL CHASE TO BE PROPERLY | | | FIRE RATED. | | | 2) NEW FABRIC AWNING SHOWN ON WEST | | | ELEVATION DRAWING TO BE FIRE RETARDANT. | | | 3) PLEASE SHOW TYPE AND NUMBER OF PIPE | | | SUPPORTS FOR FUEL PIPING. PLEASE DISPLAY | | | ROOF SUPPORTS FOR PIPING. PLEASE PROVIDE | | | PRODUCT APPROVLS FOR DAY TANK AND | | | GENERATOR. PLEASE PROVIDE MORE DETAILS | | | ON AUTOMATIC REMOTE FILLING SYSTEM. | | | ADDITIONAL MECHANICAL PERMITS REQUIRED | | | FOR FUEL SYSTEM INSTALLATION. | | | | | | CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|