2001-03-22 00:00:00REVISION #4 DATED 2/5/01
  
 A TEST REPORT OR FIRE DESIGN REFERENCE
 IS REQUIRED FOR THE SPRINKLER METHOD
 SHOWN ON SHEET A5.01 ON THE WINDOW FOR
 A TWO HOUR RATING.SEE SBC 705.1.2
  
 SHEET A6.01 AND OTHERS HAVE A NOTE
 SAYING SPRAYED FIRE PROTECTION TO BE
 APPLIED AT TENANT BUILD OUT.NO
 OCCUPANCY OF ANY PORTION OF THE
 BUILDING CAN BE ACCOMPLISHED UNLESS THE
 SHELL MEETS THE REQUIREMENTS OF FIRE
 RESISTANCE FOR TYPE II CONSTRUCTION.
 ALSO THE SPRINKLER SYSTEM MUST BE
 FUNCTIONAL REGARDLESS OF A TENANT
 OCCUPYING THE SPACE OR NOT.