| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) PLEASE PROVIDE MORE DETAILS ON FUEL | | | STORAGE TANK BELOW GENERATOR. PLEASE | | | PROVIDE CUT SHEETS ON GENERATOR AND | | | STORAGE TANK. PLEASE PROVIDE MORE | | | INFORMATION ON PHOENIX FILL PORT AND | | | ASSOCIATED PIPING AND WELDED OUTLETS. | | | PLEASE PROVIDE ANY AND ALL UL LISTINGS | | | OR FM APPROVALS FOR THESE DEVICES. | | | THE PLANS INDICATE TWO GENERATOR ROOMS. | | | HOW MANY GENERATORS AND HOW MUCH FUEL | | | IS ANTICIPATED. IS THE FILL PIPE | | | INSIDE OR OUTSIDE THE BUILDING. IF | | | OUTSIDE, IS IT PROTECTED AGAINST | | | CORROSION. IS THE PIPES LABELED. THIS | | | ARRANGEMENT IF APPROVED MUST MEET ALL | | | REQUIREMENTS OF NFPA 30, THE FLAMMABLE | | | AND COMBUSTIBLE LIQUID CODE. WHAT IS THE | | | RATING OF THE GENERATOR ROOM WALLS. | | | A SEPARATE PLANS AND PERMIT REQUIRED. | | | PLANS REVIEWED BY CAPTAIN MIKE CARSILLO | | | 659-8096,EXT.8497 | | | 835-2910 |
|