2001-01-08 00:00:001) PLEASE PROVIDE MORE DETAILS ON FUEL
 STORAGE TANK BELOW GENERATOR. PLEASE
 PROVIDE CUT SHEETS ON GENERATOR AND
 STORAGE TANK. PLEASE PROVIDE MORE
 INFORMATION ON PHOENIX FILL PORT AND
 ASSOCIATED PIPING AND WELDED OUTLETS.
 PLEASE PROVIDE ANY AND ALL UL LISTINGS
 OR FM APPROVALS FOR THESE DEVICES.
 THE PLANS INDICATE TWO GENERATOR ROOMS.
 HOW MANY GENERATORS AND HOW MUCH FUEL
 IS ANTICIPATED. IS THE FILL PIPE
 INSIDE OR OUTSIDE THE BUILDING. IF
 OUTSIDE, IS IT PROTECTED AGAINST
 CORROSION. IS THE PIPES LABELED. THIS
 ARRANGEMENT IF APPROVED MUST MEET ALL
 REQUIREMENTS OF NFPA 30, THE FLAMMABLE
 AND COMBUSTIBLE LIQUID CODE. WHAT IS THE
 RATING OF THE GENERATOR ROOM WALLS.
 A SEPARATE PLANS AND PERMIT REQUIRED.
 PLANS REVIEWED BY CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910