Plan Review Notes
Plan Review Notes For Permit 00081182
Permit Number 00081182
Review Stop E
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST RE-
 -VIEW. PLEASE NOTE THAT THE INLINE
 DISC FOR GENERATOR IS NOT SHOWN. THIS
 DISCONNECT WILL BE REQ`D AT ATS LOCATION
 AND GROUPED WITH MAINS. 230-72.
 FIRE DEPT. WILL NOT BE GOING TO THE ROOF
 TO SHUT POWER OFF AT GENERATOR IF THERE
 IS A FIRE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS FOR
 THE ABOVE PLEASE CALL. ALSO PLEASE SEE
 SHEET E3.4 AND E5.1 THEY APPEAR TO BE
 COPIES OF THE SIGNATURE? PER 61G15-23-
 -.002 MUST BE OF ORIGINAL SIGNATURE.
  
  
 DEWEY PALMER
 ELECTRICALPLAN REVIEW
 659-8096 EXT 8372