| Plan Review Notes For Permit 00081182 |
| Permit Number |
00081182 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | ******************* UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST RE- | | | -VIEW. PLEASE NOTE THAT THE INLINE | | | DISC FOR GENERATOR IS NOT SHOWN. THIS | | | DISCONNECT WILL BE REQ`D AT ATS LOCATION | | | AND GROUPED WITH MAINS. 230-72. | | | FIRE DEPT. WILL NOT BE GOING TO THE ROOF | | | TO SHUT POWER OFF AT GENERATOR IF THERE | | | IS A FIRE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS FOR | | | THE ABOVE PLEASE CALL. ALSO PLEASE SEE | | | SHEET E3.4 AND E5.1 THEY APPEAR TO BE | | | COPIES OF THE SIGNATURE? PER 61G15-23- | | | -.002 MUST BE OF ORIGINAL SIGNATURE. | | | | | | | | | DEWEY PALMER | | | ELECTRICALPLAN REVIEW | | | 659-8096 EXT 8372 |
|