Plan Review Notes
Plan Review Notes For Permit 00081182
Permit Number 00081182
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)FLOORS AND WALLS IN TOILET ROOMS SHALL
 BE NONABSORBENT TO A HEIGHT OF 4'.IF
 WALLS WILL BE PAINTED INDICATE TYPE OF
 PAINT ON THE FINISH SCHEDULE.SBC 1204.2.
  
 2)DRINKING FOUNTAINS SHALL COMPLY W/
 FACBC SEC.4.1.3.(10)(B).(IF MORE THAN
 ONE ON A FLOOR,50% SHALL COMPLY W/SEC.
 4.15.)
  
 3)CLEARLY SHOW INSIDE DIMENSIONS OF ALL
 ACCESSIBLE TOILET STALLS.IF LAV.IS
 INSTALLED ADJACENT TO THE W.C.THE MIN.
 WIDTH SHALL BE 83"PER FACBC SEC.4.17.3.
  
 4)SHT.A4.01-MIN.CLEAR FLOOR SPACE UNDER
 H.C.LAV.SHALL BE 29",NOT 27"AS SHOWN.
 FACBC SEC.4.19.2.
  
 5)SHT.A4.01-PAPER TOWEL DISPENSER,SOAP
 DISPENSER,TOILET PAPER HOLDER AND MIRROR
 SHALL BE INSTALLED ACCORDING TO FACBC
 REQS.FOR MIN.MOUNTING HEIGHTS.
  
 6)DELETE MOUNTING DETAIL FOR EWH FROM
 SHT.PO.1.
  
 7)PLUMBING PLANS STILL REFER TO "EXPRESS
 PREACTION"SYSTEM.SUBMIT DETAILS AND INFO
 FOR REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 8)FLOOR DRAIN SHALL BE INSTALLED IN LIEU
 OF HUB DRAIN.SPC 807.1.2.,807.1.3..
  
 CALL IF YOU HAVE QUESTIONS.561-659-8096
 EXT.8377.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.