| Date |
Text |
| 2001-01-08 00:00:00 | 1) BUILDING ADDRESS DOES NOT APPEAR |
| | ON ELEVATION DRAWINGS. BUILDING ADDRESS |
| | TO COMPLY WITH CITY CODE REQUIREMENTS. |
| | 2) FIRE ALARM NOTES INDICATE CLASS B, |
| | STYLE C CIRCUITS. ONLY CLASS A, STYLE |
| | D CIRCUITS ARE PERMITTED. |
| | 3) WHERE IS THE FIRE DEPARTMENT |
| | SPRINKLER AND STANDPIPE CONNECTION |
| | LOCATED. ENTIRE BUILDING IS TO BE |
| | COMPLETELY FIRE SPRINKLER PROTECTED. |
| | THIS INCLUDES ALL SERVICE ROOMS, |
| | ELECTRICAL ROOMS, AND MECHANICAL ROOMS. |
| | ALL VERTICAL SHAFTS ARE TO BE PROTECTED. |
| | THE ONLY EXCEPTION IS THE FPL VAULT |
| | ROOM. FURTHER CLARIFY THE PRE-ACTION |
| | SYSTEM LOCATIONS. WHAT APPROVALS HAVE |
| | BEEN RECEIVED TO INSTALL THESE SYSTEMS |
| | IN THE BUILDING. |
| | 4) ELEVATOR(S) TO COMPLY WITH ANSI A17.1 |
| | AND 4A-47. |
| | 5) COMPLETE FIRE ALARM SYSTEM SHOP |
| | DRAWINGS FOR THE FIRE ALARM SYSTEM |
| | EQUIPMENT SHOWN ON PLANS. THE FIRE ALARM |
| | SYSTEM IS TO BE ADDRESSABLE OR CLASS A. |
| | CUT SHEETS, WIRING DIAGRAMS, FLOOR |
| | PLANS ARE TO BE SUBMITTED. |
| | 6) EMERGENCY GENERATOR ROOM IS TO BE |
| | AT LEAST TWO HOUR FIRE SEPARATED. |
| | OPENINGS ARE TO BE PROPERLY PROTECTED. |
| | 7) NO FIRE STANDPIPE SYSTEM INFORMATION |
| | INCLUDED WITH PLANS. |
| | 8) TENANT SEPARATION REQUIREMENTS ARE TO |
| | MEET BUILDING CODE REQUIREMENTS. |