Plan Review Notes
Plan Review Notes For Permit 00081182
Permit Number 00081182
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) BUILDING ADDRESS DOES NOT APPEAR
 ON ELEVATION DRAWINGS. BUILDING ADDRESS
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 2) FIRE ALARM NOTES INDICATE CLASS B,
 STYLE C CIRCUITS. ONLY CLASS A, STYLE
 D CIRCUITS ARE PERMITTED.
 3) WHERE IS THE FIRE DEPARTMENT
 SPRINKLER AND STANDPIPE CONNECTION
 LOCATED. ENTIRE BUILDING IS TO BE
 COMPLETELY FIRE SPRINKLER PROTECTED.
 THIS INCLUDES ALL SERVICE ROOMS,
 ELECTRICAL ROOMS, AND MECHANICAL ROOMS.
 ALL VERTICAL SHAFTS ARE TO BE PROTECTED.
 THE ONLY EXCEPTION IS THE FPL VAULT
 ROOM. FURTHER CLARIFY THE PRE-ACTION
 SYSTEM LOCATIONS. WHAT APPROVALS HAVE
 BEEN RECEIVED TO INSTALL THESE SYSTEMS
 IN THE BUILDING.
 4) ELEVATOR(S) TO COMPLY WITH ANSI A17.1
 AND 4A-47.
 5) COMPLETE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR THE FIRE ALARM SYSTEM
 EQUIPMENT SHOWN ON PLANS. THE FIRE ALARM
 SYSTEM IS TO BE ADDRESSABLE OR CLASS A.
 CUT SHEETS, WIRING DIAGRAMS, FLOOR
 PLANS ARE TO BE SUBMITTED.
 6) EMERGENCY GENERATOR ROOM IS TO BE
 AT LEAST TWO HOUR FIRE SEPARATED.
 OPENINGS ARE TO BE PROPERLY PROTECTED.
 7) NO FIRE STANDPIPE SYSTEM INFORMATION
 INCLUDED WITH PLANS.
 8) TENANT SEPARATION REQUIREMENTS ARE TO
 MEET BUILDING CODE REQUIREMENTS.