Plan Review Notes
Plan Review Notes For Permit 00081182
Permit Number 00081182
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)ADDITIONAL PLUMBING FIXTURES ARE REQD.
 BASED ON SQ.FEET OF HABITABLE FLOOR
 SPACE AND OCCUPANT LOAD PER SPC TABLE
 407.SEE SPC SEC.407.1.3.FOR ALLOWED
 DEDUCTIBLE AREAS.(RE:W.C.'S,LAVS,D.F.'S)
  
 2)FLOORS AND WALLS SHALL BE NONABSORBENT
 TO A HEIGHT OF 4'PER SBC SEC.1204.2.
  
 3)DRINKING FOUNTAINS SHALL COMPLY W/
 FACBC SEC.4.1.3(10)(B).
  
 4)CLEARLY SHOW DIMENSIONS (LXW)OF THE
 H.C.TOILET STALLS.COMPLY W/FACBC SEC.
 4.17.3.(MIN.WIDTH SHALL BE 83")
  
 5)SHOW MOUNTING HEIGHT/DIMENSIONS OF ALL
 HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/FACBC 1997 ED.
  
 6)SHOW LOCATION OF H.C.URINAL ON PLAN
 AND DETAIL 30"X48"CLEAR FLOOR SPACE
 PER FACBC SEC.4.18.
  
 7)SHOW WHEELCHAIR TURNING SPACE IN
 RESTROOMS PER FACBC SEC.4.2.3.
  
 8)DIELECTRIC NIPPLES/COUPLINGS TO BE
 USED ON DISSIMILAR METALS.UNIONS NOT
 PERMITTED.309.3
  
 9)WATER HEATER SHALL BE READILY ACCESS-
 IBLE PER SPC SEC.501.7.PROVIDE FIXED
 LADDER & PLATFORM OR RELOCATE EWH TO
 FLOOR.
  
 10)SUBMIT INFO ON "EXPRESS PREACTION"
 SYSTEM.CONDENSATE CANNOT DRAIN TO
 SANITARY SYSTEM.SMC SEC.304.8.3.
  
 11)SUBMIT PAN DRAIN AND P&T RISER FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 *****NOTE:THIS PLAN REVIEW DOESN'T
 INCLUDE THE FUEL OIL PIPING SYSTEM.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.