| 2001-01-08 00:00:00 | 1)ADDITIONAL PLUMBING FIXTURES ARE REQD. |
| | BASED ON SQ.FEET OF HABITABLE FLOOR |
| | SPACE AND OCCUPANT LOAD PER SPC TABLE |
| | 407.SEE SPC SEC.407.1.3.FOR ALLOWED |
| | DEDUCTIBLE AREAS.(RE:W.C.'S,LAVS,D.F.'S) |
| | |
| | 2)FLOORS AND WALLS SHALL BE NONABSORBENT |
| | TO A HEIGHT OF 4'PER SBC SEC.1204.2. |
| | |
| | 3)DRINKING FOUNTAINS SHALL COMPLY W/ |
| | FACBC SEC.4.1.3(10)(B). |
| | |
| | 4)CLEARLY SHOW DIMENSIONS (LXW)OF THE |
| | H.C.TOILET STALLS.COMPLY W/FACBC SEC. |
| | 4.17.3.(MIN.WIDTH SHALL BE 83") |
| | |
| | 5)SHOW MOUNTING HEIGHT/DIMENSIONS OF ALL |
| | HANDICAP FIXTURES AND APPURTENANCES. |
| | COMPLY W/FACBC 1997 ED. |
| | |
| | 6)SHOW LOCATION OF H.C.URINAL ON PLAN |
| | AND DETAIL 30"X48"CLEAR FLOOR SPACE |
| | PER FACBC SEC.4.18. |
| | |
| | 7)SHOW WHEELCHAIR TURNING SPACE IN |
| | RESTROOMS PER FACBC SEC.4.2.3. |
| | |
| | 8)DIELECTRIC NIPPLES/COUPLINGS TO BE |
| | USED ON DISSIMILAR METALS.UNIONS NOT |
| | PERMITTED.309.3 |
| | |
| | 9)WATER HEATER SHALL BE READILY ACCESS- |
| | IBLE PER SPC SEC.501.7.PROVIDE FIXED |
| | LADDER & PLATFORM OR RELOCATE EWH TO |
| | FLOOR. |
| | |
| | 10)SUBMIT INFO ON "EXPRESS PREACTION" |
| | SYSTEM.CONDENSATE CANNOT DRAIN TO |
| | SANITARY SYSTEM.SMC SEC.304.8.3. |
| | |
| | 11)SUBMIT PAN DRAIN AND P&T RISER FOR |
| | REVIEW.COUNTYWIDE AMENDMENTS TO SPC |
| | SEC.104.2.1. |
| | |
| | *****NOTE:THIS PLAN REVIEW DOESN'T |
| | INCLUDE THE FUEL OIL PIPING SYSTEM. |
| | |
| | CALL 561-659-8096,EXT.8377 IF YOU HAVE |
| | ANY QUESTIONS. |
| | TIMOTHY LARGE |
| | PLUMBING PLANS EXAMINER. |