2001-01-08 00:00:00**************DENIED********************
 1.PROVIDE SHAFT DETAIL FOR DUCTS PENETR-
 ATING FROM ROOF TO 1ST FL. SHOWING COMP-
 LIANCE WITH 1997 SMC 610.4
 2.FIRE DAMPERS LOCATION AND INSTALLATION
 DETAILS TO BE SHOWN ON PLAN BY DESIGNER
 PER 1997 SMC 610.6
 3.FAN SHUT DOWN FOR UNITS WITH LESS THAN
 2000 CFM BUT SERVING AREAS USED FOR
 EGRESS SHALL HAVE FAN SHUT DOWN BY DUCT
 SMOKE DETECTOR PER 1997 SMC 406.2
 4. FAN SHUT DOWN TO BE TIED TO BUILDING
 FIRE ALARM SYSTEM PER NFPA 90A 4-4.4
 5. MODEL COUNTYWIDE AMENDMENTS AS ADOPTE
 D BY ORDINANCE REQUIRES EQUIPMENT MOUNT-
 ED ON ROOF TO HAVE MIN. 18" CLEARANCE
 FOR ACCESS TO ROOF MATERIALS UNDERNIETH
 FROM ROOF SURFACE TO BOTTOM OF MAIN
 SUPPORT STRUCTURE OF STAND