| Plan Review Notes For Permit 00081182 |
| Permit Number |
00081182 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | **************DENIED******************** | | | 1.PROVIDE SHAFT DETAIL FOR DUCTS PENETR- | | | ATING FROM ROOF TO 1ST FL. SHOWING COMP- | | | LIANCE WITH 1997 SMC 610.4 | | | 2.FIRE DAMPERS LOCATION AND INSTALLATION | | | DETAILS TO BE SHOWN ON PLAN BY DESIGNER | | | PER 1997 SMC 610.6 | | | 3.FAN SHUT DOWN FOR UNITS WITH LESS THAN | | | 2000 CFM BUT SERVING AREAS USED FOR | | | EGRESS SHALL HAVE FAN SHUT DOWN BY DUCT | | | SMOKE DETECTOR PER 1997 SMC 406.2 | | | 4. FAN SHUT DOWN TO BE TIED TO BUILDING | | | FIRE ALARM SYSTEM PER NFPA 90A 4-4.4 | | | 5. MODEL COUNTYWIDE AMENDMENTS AS ADOPTE | | | D BY ORDINANCE REQUIRES EQUIPMENT MOUNT- | | | ED ON ROOF TO HAVE MIN. 18" CLEARANCE | | | FOR ACCESS TO ROOF MATERIALS UNDERNIETH | | | FROM ROOF SURFACE TO BOTTOM OF MAIN | | | SUPPORT STRUCTURE OF STAND |
|