| Plan Review Notes For Permit 00081182 |
| Permit Number |
00081182 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2001-01-08 00:00:00 | 1) NO FIRE SPRINKLER DRAWINGS INCLUDED | | | IN PLANS. | | | 2) NO INFORMATION ON FIRE ALARM | | | EQUIPMENT PRESENTLY IN OR PLANNED FOR | | | THE BUILDING. | | | 3) FUTURE CORRIDORS ARE TO BE AT LEAST | | | ONE HOUR FIRE RATED. | | | 4) NO INFORMATION ON STANDPIPE SYSTEM | | | PRESENTLY IN OR PLANNED FOR THE BUILDING | | | 5) PLEASE PROVIDE MORE DETAILS ON TWO | | | HOUR FIRE RATED FLOOD SPRINKLER SYSTEM | | | ON PAGE A5.01 | | | 6) EMERGENCY GENERATOR ROOM TO BE AT | | | LEAST TWO HOUR FIRE RATED AND MEET THE | | | REQUIREMENTS OF NFPA 30, SINCE THE | | | GENERATOR WILL HAVE SUB BASE TANK. | | | 7) EMERGENCY LIGHTS AND EXIT SIGNS OF | | | PROPER AMOUNT ARE TO PRESENT IN ALL | | | MEANS OF EGRESS. | | | 8) CODE ANALYSIS BOX INCORRECT. IF | | | SAFETY 1994 MEANS THE LIFE SAFETY CODE, | | | IT SHOULD READ SAFETY 1985. |
|