Plan Review Notes
Plan Review Notes For Permit 00081182
Permit Number 00081182
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO FIRE SPRINKLER DRAWINGS INCLUDED
 IN PLANS.
 2) NO INFORMATION ON FIRE ALARM
 EQUIPMENT PRESENTLY IN OR PLANNED FOR
 THE BUILDING.
 3) FUTURE CORRIDORS ARE TO BE AT LEAST
 ONE HOUR FIRE RATED.
 4) NO INFORMATION ON STANDPIPE SYSTEM
 PRESENTLY IN OR PLANNED FOR THE BUILDING
 5) PLEASE PROVIDE MORE DETAILS ON TWO
 HOUR FIRE RATED FLOOD SPRINKLER SYSTEM
 ON PAGE A5.01
 6) EMERGENCY GENERATOR ROOM TO BE AT
 LEAST TWO HOUR FIRE RATED AND MEET THE
 REQUIREMENTS OF NFPA 30, SINCE THE
 GENERATOR WILL HAVE SUB BASE TANK.
 7) EMERGENCY LIGHTS AND EXIT SIGNS OF
 PROPER AMOUNT ARE TO PRESENT IN ALL
 MEANS OF EGRESS.
 8) CODE ANALYSIS BOX INCORRECT. IF
 SAFETY 1994 MEANS THE LIFE SAFETY CODE,
 IT SHOULD READ SAFETY 1985.