2001-01-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE 230-70 AND 230-72
 FOR REQ`MENTS OF AN INLINE DISC FROM
 GENERATOR TO ATS.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 AND INCLUDE 125% FOR ALL CONTINUOUS
 LOADS. PER 215-3
  
 3)NOTE: PLEASE SHOW WIRE SIZES ON ONE
 LINE DIAGRAM FOR GENERATOR CONDUCTORS.
 PIPE SIZE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372